Description

Product Description | |
Measurement | Electrochemical |
Sensor Agency Approvals | Sensor is UL Recognized for ASNI/UL-2034 and UL-2075, E240671 |
Measurement Range | 0-100, 150, 300, 400, or 500 ppm (selectable) |
Accuracy | ±5 ppm or ±5% of reading (whichever is greater) |
Accuracy Rated | 0 to 50°C (32 to 122°F), 15 to 95 %RH |
Life Expectancy | 5-7 years in air |
Typical Coverage Area | 700m2 (7500ft2) or 15m (50ft) radius |
Operating Conditions | -20 to 50°C (-4 to 122°F), 15 to 95 %RH, 0.9 to 1.1 atm |
Sample Method | Diffusion or flow through sample tube for duct mounted models |
Stability | <5% signal loss/year |
Response Time | <35 seconds for 90% step change |
Power Supply | 24 Vdc ±20% or 24 Vac ±10% (non-isolated half-wave rectified) |
Consumption | 100 mA maximum with all options on |
Protection Circuitry | Reverse voltage protected and output limited |
Output Signal | 4-20 mA (Active), 0-5 or 0-10 Vdc (Selectable) |
Output Drive | Current: 450Ω maximum Voltage: 10 KΩ minimum |
Output Resolution | 10 bit PWM (±0.4ppm) |
Lcd Display | Displays PPM and menu parameters 1ppm, 35mm W x 15mm H (1.$” x 0.6”) Alpha-numeric 2 line x 8 character with backlight |
Status Led | 2 color (re/green) on front panel |
OPTIONAL RELAY OUTPUT | One or two Form C (N.O. and N.C.) 5 Amps @ 250 Vac, 5 Amps @ 30 Vdc, p.f. = 1 Relay 1 Trip Point: Programmable 20-500 ppm in 10 ppm increments Relay 2 Trip Point: Programmable 20-500 ppm in 10 ppm increments Relay Hysteresis: Programmable 10-100 ppm in 5 ppm increments Relay Delay: Programmable 0-10 minutes in 1 minute increments |
Enclosure | ABS, UL94-V0, IP65 (NEMA 4) |
Enclosure Dimensions | 145mm W x 101mm H x 240mm D (5.7” x 4” x 9.4”) |
Field Calibration | By applying calibration gas standard (contact Greystone for calibration kit) |
Country Of Origin | Canada |
DataSheet | Downloads> |