Description

Specification | |
---|---|
BACnet Support: | Conforms to the BACnet Building Controller (B-BC) Standard Device as defined in BACnet 135-2001 Annex L. BTL Listing BACnet PICS |
Brand/ Manufacturer | ALC |
Communication Ports: | ME812u Model EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP ME812u-E Model Ethernet port (10/100Mbps) only for BACnet over Ethernet communications EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP ME812u-LGR Model Ethernet port* (10/100Mbps) for BACnet/IP or BACnet over Ethernet communications EIA-485 port for ARCNET 156 Kbps or BACnet MS/TP (9600 baud to 76.8 Kbps) EIA-232/485 port* configurable port for BACnet PTP *Third-Party integration drivers available through Ethernet and (1) EIA-232/485 configurable port All Models have Rnet port for Rnet communicating devices such as ZS room sensors and Touch interfaces. Xnet (500 Kbps) port for MEx I/O expansion modules. Local access port. |
Universal Inputs: | Twelve configurable universal inputs with 14-bit A/D resolution. Supported input types include: 0-5 V-dc, 0-10 V-dc, 0-20 mA, Thermistor (10k Ohm Type II), 1k Ohm RTD (Platinum, Nickel or Balco), and Dry Contact. All inputs support pulse counting up to 40 cycles per second (25mSec minimum pulse). |
Universal Outputs: | Eight universal outputs are jumper configurable as 0-10V-dc, or 0-20mAdc with 12-bit A/D or 24V-dc @ 50mA relay drive. HOA (hand/off/auto) switches for all outputs, including potentiometer for manual adjustment of analog outputs |
Expansion: | Six MEx I/O expansion modules can be connected – one mounted directly on top of the controller, mounted locally in a stack configuration or remote-mounted up to 100ft away. |
Microprocessor: | Powerful 32-bit Motorola Power PC microprocessor. High-performance 32-bit communication co-processor. I/O expansion CAN co-processor |
Memory: | 32-bit memory bus structure, 8 Mbyte flash memory, 16 Mbyte SDRAM battery-backed. Battery CR123A has life of 10 years with 720 hours of cumulative power outage |
Real-time Clock: | Battery-backed real-time clock |
Status Indicator: | LED status indicators for EIA-232/485 communication, and low battery status. Seven-segment status display for running, error, and power status |
Module Addressing: | Rotary dip switches for intuitive network addressing of modules. |
Protection: | Built-in surge and transient protection circuitry for power, communications and I/O |
Listed by: | UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 – Subpart B |
Weight: | 1.4 lb |
Dimensions: Overall Width | Width: 7-1/2” (190mm) Height: 11-5/16” (287mm) Depth: 1-1/4” (32mm) m… |
Mounting Holes : | Width: 5” (127mm) Height: 10-7/8” (276mm) |