Specification | |
---|---|
BACnet Support: | Conforms to the Advanced Application Controller (B-AAC) Standard Device Profile as defined in ANSI-ASHRAE Standard 135-2004 (BACnet) Annex L. |
Brand/ Manufacturer | ALC |
Communication Ports: | The following ports are available: EIA-485 port for ARCNET 156 Kbps or MS/TP (9600 bps – 76.8 Kbps) Local access port for system start-up and troubleshooting Rnet port for sensors and local operator interfaces |
Binary Outputs: | Two binary outputs, relay contact rated at 1A max @ 24V-ac, configured normally open |
Universal Inputs: | Two inputs with 10-bit A/D resolution for dry contact or Type 2 thermistors |
Microprocessor: | High-speed 16-bit microprocessor with ARCNET communication co-processor |
Memory: | 512 KByte non-volatile battery-backed RAM, 1 MByte flash memory, 16-bit memory bus |
Status Indicators: | LED status indicators for EIA-485 communication, running, error, power and all binary outputs |
Module Addressing: | Rotary dip switches for intuitive network addressing of modules |
Listed By | UL916 (Canadian Std C22.2 No. 205-M1983), CE, FCC Part 15 – Subpart B – Class A |
Addressing: | Rotary dip switches for intuitive network addressing. |
Environmental Operating Range: | 0F to 13oF (-17.8C to 54.4oC); 10 to 90% relative humidity, non-condensing |
Power Requirement: | 24 V-ac ± 10%, 26 V-dc (25 V min, 30 V max), 50 to 60Hz, 12 VA. |
Physical: | Rugged GE C2950 Cycoloy plastic |
Weight: | 0.6lb |
Dimensions: Overall | Width: 5-1/16” (129mm) Height: 5-11/16” (144mm) Depth: 1-1/2” (38mm) min. panel depth |
Mounting: | Two mounting holes center line as at left with 5-5/16” (135mm) spacing (h… |